Type 1 protectors. Iimp= 100kA. Vía de chispas.
Transientovervoltage protector, designed to protect lines where the risk of direct lightningdischarge is high, in single-phase installations.
It is installed in the meter area, in parallel with the power supply network, so that the service current does not pass through the equipment.
This content is restricted.
You need to be logged in to download the manuals.
CODE | REFERENCE |
10002711 | V2T-100 |
SPECIFICATIONS | VALORES |
Rated voltage Un | 240 VAC (L1/N, L2/N, L3/N) |
Maximum voltage Uc | 385 VAC (L/N) |
Frequency | 50-60 Hz |
Protection level Up | ≤2kV (L/N) ≤ 2,5kV (PE/N) |
Impulse intensity (10/350µs) Iimp | 50 kA (L/N) 100kA (N/PE) |
Rated current In (8/20µs) | 50 kA |
Overvoltage response time | ≤100 ns |
Maximum pre-fuse | 500A gL |
Maximum cable cross-section at terminals | 35 mm2 |
Temperature ranges | -40º +85ºC |
Degree of protection | IP20 |
Mounting | Rail DIN 35 |
Product standards | IEC 61643-11 / EN 61643-11 |
Tipo/Clase | I |
A Class II protector must be installed downstream of this device.
This equipment DOES NOT PROTECT against PERMANENTpower surges.
PRODUCTS RELATED
CONTACT WITH US
Development and manufacturing of electronic products and system integration: pump protection, level control and surge protection.
Contact
© Toscano 2021 · All rights reserved | Quality and environmental policy |Legal notice | Privacy policy | Cookie policy
Si tienes preguntas o ideas que te gustaría compartir, envía un mensaje. Para algo más específico, por favor usa nuestros teléfonos de contacto.
Departamento comercial
Dirección
If you have questions or ideas you’d like to share, send us a message. For something more specific, please use one of the addresses below.
SalesDepartment
TechnicalSupport
Address