V2T-12,5/50B

Transient, two-phase, Type 1+2, 12.5/50kA

Description

Module for protection against transient overvoltages caused by atmospheric discharges, switching operations in electrical circuits and electrostatic discharges.

For BIPHASEcircuits, phase+phase, it is not valid for phase+neutral circuits, in this caseV2T-12,5/50 must be used.

It avoids the damage that these transient overvoltages may cause to the equipment supplied by this network.

Downloads

(EN) User Manual - V2T-125/50B - ED2.20.pdf Download

Technical Specifications

SPECIFICATIONS VALUE
Rated voltage Un 230 Vac
Maximum voltage Uc 320Vac (L/L)
Frequency 50-60Hz
Protection level Up <1,5kV (L/L) /<1,5 kV (L/PE)
Impulse current (10/350us) Iimp 12,5kA (L/L)
Maximum discharge current (8/20μs) Imax. 50kA (L/L)
Rated discharge current (8/20μs) In 20kA (L/L)
Surge response time ≤25ns
Pre-fuse protection 160A gL
Maximum cable cross-section at terminals 35 mm2
Temperature ranges -40º +80ºC / 80%
Degree of protection IP20
No. of DIN modules 2
Mounting Rail DIN 35
Type 1+2
Directives 2014-35-UE (LVD) 2014-30-UE (EMC) 2011-65-UE (RoHS)

Codes and references

CODE REFERENCE
10003080 V2T-12,5/50B

you may also be interested in

PRODUCTS RELATED

need a quote or information?

CONTACT WITH US

sobretensión

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.