FV-S

Transient overvoltage protection type 2 for photovoltaic systems. Imax= 40kA. With relay output.

Description

This series of protectors for photovoltaic systemshave been developed to protect against discharges and surges produced by lightning strikes on the DC side of such systems.

The protection consists of three stages of varistors equipped with thermal disconnectors that indicate through a window the failure of the element. It has a remote output (indication contact).

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - FV-S.pdf Download
(ES) Manual de usuario - FV-S - ED2.22.pdf Download

Technical Specifications

SPECIFICATIONS VALUE
Rated voltage (Unpv) 600 / 1250VDC (según modelo)
Maximum voltage DC+/DC- (Ucpv) 750 / 1500 VDC (según modelo)
Nominal discharge current 8/20 (In) 20 kA
Maximum discharge current (Imax) 40 kA
Nivel de protección (Arriba) <2.8 / <encoded_tag_open 5.2 kV (depending on model)
Response time (ta) ≤25 nS
Operating temperature -40 a +80 ºC
Degree of protection IP20
Fault indication Window
Maximum connection cross-section 25 mm2 (FV-600/2S), 35 mm2 (FV-1250/3S), remote: 1,5 mm2
Remote indication (contact) 250 V~ / 0,5 A 30 V= / 1 A
Tipe 2
Directives 2014-35-UE (LVD) 2014-30-UE (EMC) 2011-65-UE (RoHS)

Codes and references

CODE REFERENCE
10002686 FV-600/2S
10003443 FV-800/3S
10002687 FV-1250/3S

you may also be interested in