Pump control with hydrolevel by buoys or probes

Description

Pump controller with hydro level

  • Well(emptying) or tank(filling) control
  • Control by conductive probe or buoys
  • Module can be plugged into a standardized socket.

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - EASY-LEVEL.pdf Download
(FR) Manuel de l’utilisateur - EASY-LEVEL - ED2.pdf Download
(ES) Manual de usuario - EASY-LEVEL - ED2.pdf Download
(EN) User manual - EASY-LEVEL - ED2.pdf Download

Technical Specifications

SPECIFICATIONS VALUE
Signage Voltage and Pump Relay
Operating voltage 230 V AC - 50/60 Hz
Contacto utilización 12 A - 250 V AC
Power consumption 1,8 VA
Permissible voltage variations +10%...-20%
Rearming time Fixed for 15 minutes
Response sensitivity 60 to 100 Kohm
Voltage on probes / floats 12 V AC / 50 Hz
Intensity in probes / floats 1.2 mA max. in short circuit
Sección máxima de los terminales 3x2,5 mm2
Working temperature -10...+60 ºC
Indice de protección IP40
Dimensions (WxDxH) 62x123x73 mm
Net weight 240 g (470 g with 3 SN probes included)

Codes and references

CODES REFERENCES
10002698 EASY-LEVEL