V2T-12,5/50

Switchboard protectors. Protection type 1+2. Imax= 12,5/50kA

Description

Protector against transientovervoltages caused by atmospheric discharges, switching operations in electric circuits and electrostatic discharges in single-phase installations.

In the event of a transient overvoltage, the equipment absorbs it by shunting it to ground (PE), thus preventing it from causing any damage to the devices connected to the network.

If, due to an overvoltage, the protection becomes inoperative, the equipment will display the warning window in red. In this case, the protective module will have been rendered unusable and must be replaced by another, pluggable and easily replaceable module.

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - V2T-12,5/50.pdf Download
(ES)Manual V2T-125-50 ED4_20-ES Download

Technical Specifications

SPECIFICATIONS VALORES
Rated voltage Un 230Vac (L/N)
Maximum voltage Uc 320Vac (L/N) 255Vac (N/PE)
Frequency 50-60Hz
Protection level Up <1,5kV (L/N) /<1,5 kV (N/PE)
Impulse current (10/350us) Iimp 12,5kA (L/N) 25kA (N/PE)
Intensidad máxima de descarga (8/20μs) Imax. 50kA (L/N) 100kA (N/PE)
Corriente nominal de descarga (8/20μs) In 20kA (L/N) 25kA (N/PE)
Surge response time ≤25ns
Pre-fuse protection 160A gL
Maximum cable cross-section at terminals 35mm2
Temperature ranges -40º +80ºC / 80%
Degree of protection IP20
No. of DIN modules 2
Mounting Rail DIN 35
Standards IEC 61643-11 / EN 61643-11
Clase / Tipo I+II

Codes and references

CODE REFERENCE
10003021 V2T-12,5/50

you may also be interested in

PRODUCTS RELATED

need a quote or information?

CONTACT WITH US

sobretensión

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.