V3T-100

Type 1 protectors. Iimp= 100kA. Vía de chispas

Description

Transientovervoltage protector, designed to protect lines where the risk of direct lightningdischarge is high, in three-phaseinstallations.

It is installed in the meter area or in the housing panel, in parallel with the power supply network, so that the service current does not pass through the equipment.

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - V3T-100.pdf Download
(ES) Manual de usuario - V3T-100 - ED6.21.pdf Download

Technical Specifications

SPECIFICATIONS VALUE
Rated voltage Un 240 VAC (L/N)
Maximum voltage Uc 385 VAC (L/N)
Frequency 50-60 Hz
Protection level Up ≤ 2,5kV (L/N) ≤ 2kV (N/PE)
Impulse intensity (10/350µs) imp 50 kA (L/N) 100kA (N/PE)
Rated current In (8/20µs) 50 kA (L/N) 100kA (N/PE)
Surge response time ≤100 ns
Maximum pre-fuse 500A gL
Maximum cable cross-section at terminals 35 mm2
Minimum cable cross-section at terminals 10 mm2
Temperature ranges -40º +80ºC
Degree of protection IP20
Mounting Rail DIN 35
No. of DIN modules 8
Tipe 1
Directives 2014-35-UE (LVD) 2014-30-UE (EMC) 2011-65-UE (RoHS)

Codes and references

CODE REFERENCE
10002140 V3T-100

you may also be interested in

PRODUCTS RELATED

need a quote or information?

CONTACT WITH US

sobretensión

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.