V3T-12,5/50

Transient, three-phase, Class I+II

Description

Protector against transientovervoltages, caused by atmospheric discharges, switching operations in electric circuits and electrostatic discharges, in three-phase installations.

In the event of a transient overvoltage, the equipment absorbs it by shunting it to ground (PE), thus preventing it from causing any damage to the devices connected to the network.

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - V3T-12,5/50.pdf Download
(ES) Manual de usuario - V3T-12.5/50 - ED6.21.pdf Download

Technical Specifications

SPECIFICATIONS VALUE
Rated voltage Un 230 Vac (L/N) 400Vac (L/L)
Maximum voltage Uc 320Vac (L/N) 255Vac (N/PE)
Frequency 50-60Hz
Protection level Up <1,5kV (L/N) /<1,5 kV (N/PE)
Impulse current (10/350us) Iimp 12,5kA (L/N) 25kA (N/PE)
Maximum discharge current (8/20μs) Imax 50kA (L/N) 100kA (N/PE)
Corriente nominal de descarga (8/20μs) In 20kA (L/N) 25kA (N/PE)
Surge response time ≤25ns
Pre-fuse protection 160A gL
Maximum cable cross-section at terminals 35 mm2
Temperature ranges -40º +80ºC / 80%
Degree of protection IP20
No. of DIN modules 4
Mounting Rail DIN 35
Tipe 1+2
Directives 2014-35-UE (LVD) 2014-30-UE (EMC) 2011-65-UE (RoHS)

Codes and references

CODE REFERENCE
10003022 V3T-12,5/50

you may also be interested in

PRODUCTS RELATED

need a quote or information?

CONTACT WITH US

sobretensión