V3T-25/50

Protectors for meter centralization. Protection type 1+2. Imax= 25/50kA. Vía de chispas.

Description

Surge arrester designed for lines where the risk of direct lightningdischarge is high, in three-phase installations.

It is installed in the meter area or in the housing panel, in parallel with the power supply network, so that the service current does not pass through the equipment.

Downloads

(ES) Declaración UE de conformidad / (EN) EU Declaration of Conformity - V3T-25/50.pdf Download
(ES) Manual de usuario - V3T-25/50 - ED6.20.pdf Download

Technical Specifications

SPECIFICATIONS VALORES
Rated voltage Un 240 VAC
Maximum voltage Uc 385 VAC
Frequency 50-60 Hz
Protection level Up ≤2 kV (PE/N) ≤2 kV (L/N)
Impulse intensity (10/350μs) Iimp 25 kA (L/N) 50 kA (N/PE)
Maximum discharge current ((8/20μs) Imax 100 kA
Rated current (8/20μs) In 25 kA (L/N) 50 kA (N/PE)
Surge response time ≤100 ns
Maximum cable cross-section at terminals 35 mm²
Maximum pre-fuse 325 A gL
Mounting Rail DIN 35
Product standards IEC 61643-11 / EN61643-11
Tipe 1 + 2
Temperature ranges -40º… +85º C
Degree of protection IP20
Fault indication Window
No. of DIN modules 8

Codes and references

CODE REFERENCE
10003245 V3T-25/50

need a quote or information?

CONTACT WITH US

sobretensión

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.